MCB Size Calculator
MCB Size Calculator
Turn a load in watts or amps into a design current and the next standard MCB rating from the IEC 60898-1 preferred list — with the trip curve that suits the load and the check that matters most: the breaker must protect the cable.
MCB rating for a load
a 3,000 W geyser at 230 V single-phase, power factor 1, with the NEC’s 125% continuous-load factor
Design current and rating
- IB
- design current: the current the circuit is meant to carry
- In
- rated current of the breaker, from the preferred list
- IZ
- the cable’s derated current-carrying capacity, from your code
- I₂
- the current at which the breaker trips conventionally: 1.45 × In for an MCB, which is why I₂ ≤ 1.45 IZ is satisfied automatically when In ≤ IZ
Worked example
a 3,000 W geyser at 230 V single-phase, power factor 1, with the NEC's 125% continuous-load factor
IB = 3,000 ÷ (230 × 1) = 13.04 A
Design current = 13.04 × 1.25 = 16.30 A
Next preferred rating at or above it: 20 A (16 A would be next below, and is the answer if you size on the design current alone)
Curve C: it will not trip instantaneously below 100 A and must by 200 A; thermally it holds 22.6 A for an hour and must trip by 29.0 A
The cable must then be good for at least 20 A after derating — check Iᴢ in your code’s table before accepting this rating
Trip curves (IEC 60898-1 instantaneous tripping ranges)
| Curve | Instantaneous trip | Example at 16 A | Typical use |
|---|---|---|---|
| B | 3 to 5 × In | 48–80 A | Resistive and lighting circuits, sockets, long cable runs in domestic installations |
| C | 5 to 10 × In | 80–160 A | Mixed loads with moderate inrush: small motors, fluorescent and LED lighting banks, air conditioners |
| D | 10 to 20 × In | 160–320 A | High inrush: transformers, welding sets, capacitor banks, larger motors started direct on line |
Design current for common loads (computed by this page)
| Load | Assumed | Design current | Rating at 100% | Rating at 125% |
|---|---|---|---|---|
| LED lighting circuit | 400 W at 230 V, PF 0.9 | 1.93 A | 6 A | 6 A |
| Sockets, general purpose | 2,300 W at 230 V, PF 1.0 | 10.00 A | 10 A | 13 A |
| Water heater (geyser) | 3,000 W at 230 V, PF 1.0 | 13.04 A | 16 A | 20 A |
| 1.5 ton air conditioner | 1,600 W at 230 V, PF 0.9 | 7.73 A | 8 A | 10 A |
| Induction hob | 3,600 W at 230 V, PF 1.0 | 15.65 A | 16 A | 20 A |
| 1 HP water pump | 900 W at 230 V, PF 0.8 | 4.89 A | 6 A | 8 A |
| 11 kW three-phase machine | 11,000 W at 415 V, PF 0.85 | 18.00 A | 20 A | 25 A |
Choosing an MCB rating
A miniature circuit breaker does two jobs with two mechanisms. A bimetallic strip handles slow overloads: it bends as it warms, and the more the current exceeds the rating the sooner it trips. An electromagnet handles short circuits: above a multiple of the rating it throws the contacts open in milliseconds. The rating In is the current it will carry indefinitely; to IEC 60898-1 it must not trip within an hour at 1.13 × In (22.6 A for a 20 A device) and must trip within that hour at 1.45 × In (29.0 A).
Start from the design current. Work out what the circuit will actually draw — watts ÷ (volts × power factor), or √3 × volts × power factor for three-phase — then apply whatever continuous-load factor your code demands. The NEC requires the device and the conductor to be sized at 125% of a load that runs three hours or more; IEC 60364 and IS 732 instead require only IB ≤ In ≤ IZ, with the inrush of motors handled by the trip curve rather than by oversizing. Take the next preferred rating at or above the result.
The breaker protects the cable, not the appliance. This is the point people get wrong. If a 16 A cable is protected by a 32 A breaker, a 25 A fault will sit there heating the insulation forever without ever tripping. Never fit a larger breaker to stop nuisance tripping: find out why it trips. If the circuit genuinely needs more current, the cable has to grow first. Enter the cable’s derated ampacity above and the page checks In against it.
Curves. B, C and D differ only in the instantaneous threshold — 3–5, 5–10 and 10–20 times the rating. A motor drawing six times its running current for a second will trip a B curve and hold on a C; a transformer’s magnetising inrush may need a D. But a higher curve needs more fault current to operate quickly, so on a long circuit with a high earth-fault loop impedance a D curve may not clear a fault in the required time at all. That calculation — loop impedance, disconnection time, breaking capacity (6 kA or 10 kA), discrimination with the upstream device and the RCD or RCBO for shock protection — is the electrician’s, not this page’s.
Size the cable for the drop with the voltage drop calculator or the wire size calculator, convert the load with the watts to amps calculator, and check what it all costs with the electricity consumption calculator.
Frequently asked questions
What size MCB do I need for a 3 kW geyser?
At 230 V and unity power factor the load is 13.04 A. Sized on the design current alone that is a 16 A device; with the NEC’s 125% continuous-load factor it is 16.30 A, so 20 A. Either way the cable must be good for the rating you choose.
What is the difference between B, C and D curves?
Only the instantaneous trip threshold: B trips between 3 and 5 times the rating, C between 5 and 10, D between 10 and 20. Use B for lighting and resistive loads, C for mixed and small-motor loads, D for heavy inrush. The slow-overload behaviour is identical.
Can I fit a bigger MCB to stop it tripping?
No. The breaker is sized to protect the cable; a larger one leaves the cable unprotected. Find the cause — an overloaded circuit, a faulty appliance or a genuine fault — or have the circuit rewired in larger cable and then uprated.
Is an MCB the same as an RCD or RCBO?
No. An MCB protects against overload and short circuit; an RCD detects current leaking to earth and protects people. An RCBO is both in one module. Most codes now require residual-current protection on socket and wet-area circuits as well as the MCB.
What are the standard MCB ratings?
IEC 60898-1’s preferred values are 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A; 8 A and 13 A are rarely stocked outside a few markets, and ratings below 6 A are also made. Above 125 A the device is a moulded-case circuit breaker to IEC 60947-2.
Related calculators
References
- IEC 60898-1:2015, Circuit-breakers for overcurrent protection for household and similar installations: preferred rated currents and the type B, C and D instantaneous tripping ranges (reproduced in BEAMA, Guide to Low Voltage Circuit-breaker Standards, March 2022).
- IEC 60364-4-43:2008, Low-voltage electrical installations — Protection against overcurrent, clause 433.1: IB ≤ In ≤ IZ and I2 ≤ 1.45 × IZ.
- NFPA 70, National Electrical Code: 210.19(A)(1) and 210.20(A) (noncontinuous load plus 125% of the continuous load) and the informational notes to 210.19(A) and 215.2(A) (3% branch, 5% total voltage drop, advisory).
- IS 732:2019, Code of practice for electrical wiring installations (Bureau of Indian Standards).
- Schneider Electric, Complementary technical information — tripping curves (CA908024E, 2021): the conventional thermal points for EN 60898-1, 1.13 In (no trip) and 1.45 In (trip).