AWG Wire Size Calculator

AWG Wire Size Calculator

Diameter, cross-sectional area and resistance of any American Wire Gauge size from 4/0 to 40, for copper and aluminium — and the reverse: the AWG size nearest to a metric area in mm².

AWG gauge properties

AWG ⇄ diameter, mm², Ω/km
In the second mode this shows the nearest gauge to the area you enter.
A metric conductor size, e.g. 1.5, 2.5, 4, 6 or 10 mm². In the first mode it shows the gauge’s area.
The solid conductor's cross-section drawn to scale (the bar below is 5 mm), from 4/0 down to 40 AWG. Very fine gauges shrink to a dot. A stranded conductor of the same gauge is slightly larger overall.
2.053mmExample

12 AWG copper

Advertisement

The AWG formulas (ASTM B258)

d = 0.127 mm × 92(36 − n) / 39;   A = π d² ÷ 4;   R = ρ ÷ A;   reverse: n = 36 − 39 × log92(d ÷ 0.127 mm)
n
the gauge number; 1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3
d
diameter of the solid conductor; 36 AWG is exactly 0.005 in (0.127 mm) and 4/0 is 0.46 in
A
cross-sectional area; circular mils = (d in thousandths of an inch)²
ρ
resistivity at 20 °C: copper 0.017241, aluminium 0.028264 Ω·mm²/m

Worked example

12 AWG copper
d = 0.127 × 92(36 − 12)/39 = 0.127 × 920.6154 = 2.053 mm (0.0808 in)
A = π × 2.053² ÷ 4 = 3.309 mm², or 6,529.9 circular mils
Copper: 0.017241 ÷ 3.309 = 0.005211 Ω/m = 5.211 Ω/km, or 1.588 Ω per 1,000 ft
Aluminium: 0.028264 ÷ 3.309 × 1,000 = 8.542 Ω/km

AWG sizes, 4/0 to 40

AWGDiameter (mm)Diameter (in)Area (mm²)Copper, 20 °CAluminium, 20 °C
4/0 (0000)11.6840.4600107.2160.8 mΩ/km263.6 mΩ/km
3/0 (000)10.4050.409685.03202.8 mΩ/km332.4 mΩ/km
2/0 (00)9.2660.364867.43255.7 mΩ/km419.2 mΩ/km
1/0 (0)8.2510.324953.48322.4 mΩ/km528.5 mΩ/km
17.3480.289342.41406.6 mΩ/km666.5 mΩ/km
26.5440.257633.63512.7 mΩ/km840.4 mΩ/km
35.8270.229426.67646.4 mΩ/km1.06 Ω/km
45.1890.204321.15815.2 mΩ/km1.336 Ω/km
54.6210.181916.771.028 Ω/km1.685 Ω/km
64.1150.162013.31.296 Ω/km2.125 Ω/km
73.6650.144310.551.634 Ω/km2.679 Ω/km
83.2640.12858.3662.061 Ω/km3.379 Ω/km
92.9060.11446.6342.599 Ω/km4.26 Ω/km
102.5880.10195.2613.277 Ω/km5.372 Ω/km
112.3050.09074.1724.132 Ω/km6.774 Ω/km
122.0530.08083.3095.211 Ω/km8.542 Ω/km
131.8280.07202.6246.571 Ω/km10.77 Ω/km
141.6280.06412.0818.285 Ω/km13.58 Ω/km
151.4500.05711.6510.45 Ω/km17.13 Ω/km
161.2910.05081.30913.17 Ω/km21.6 Ω/km
171.1500.04531.03816.61 Ω/km27.23 Ω/km
181.0240.04030.82320.95 Ω/km34.34 Ω/km
190.9120.03590.652726.41 Ω/km43.3 Ω/km
200.8120.03200.517633.31 Ω/km54.6 Ω/km
210.7230.02850.410542 Ω/km68.85 Ω/km
220.6440.02530.325552.96 Ω/km86.82 Ω/km
230.5730.02260.258266.78 Ω/km109.5 Ω/km
240.5110.02010.204784.21 Ω/km138.1 Ω/km
250.4550.01790.1624106.2 Ω/km174.1 Ω/km
260.4050.01590.1288133.9 Ω/km219.5 Ω/km
270.3610.01420.1021168.9 Ω/km276.8 Ω/km
280.3210.01260.08098212.9 Ω/km349 Ω/km
290.2860.01130.06422268.5 Ω/km440.1 Ω/km
300.2550.01000.05093338.5 Ω/km555 Ω/km
310.2270.00890.04039426.9 Ω/km699.8 Ω/km
320.2020.00800.03203538.3 Ω/km882.5 Ω/km
330.1800.00710.0254678.8 Ω/km1.113 kΩ/km
340.1600.00630.02014856 Ω/km1.403 kΩ/km
350.1430.00560.015971.079 kΩ/km1.769 kΩ/km
360.1270.00500.012671.361 kΩ/km2.231 kΩ/km
370.1130.00450.010051.716 kΩ/km2.813 kΩ/km
380.1010.00400.0079672.164 kΩ/km3.548 kΩ/km
390.0900.00350.0063182.729 kΩ/km4.474 kΩ/km
400.0800.00310.005013.441 kΩ/km5.641 kΩ/km
Computed from the ASTM B258 formula; the inch column matches the standard’s rounded table. Resistance per kilometre of solid conductor, DC.

Metric sizes and their AWG neighbours

Metric sizeExact gaugeNearest AWGSmallest AWG at least as large
0.5 mm²20.1520 (0.518 mm²)20 (0.518 mm²)
0.75 mm²18.4018 (0.823 mm²)18 (0.823 mm²)
1 mm²17.1617 (1.04 mm²)17 (1.04 mm²)
1.5 mm²15.4115 (1.65 mm²)15 (1.65 mm²)
2.5 mm²13.2113 (2.62 mm²)13 (2.62 mm²)
4 mm²11.1811 (4.17 mm²)11 (4.17 mm²)
6 mm²9.439 (6.63 mm²)9 (6.63 mm²)
10 mm²7.237 (10.5 mm²)7 (10.5 mm²)
16 mm²5.205 (16.8 mm²)5 (16.8 mm²)
25 mm²3.283 (26.7 mm²)3 (26.7 mm²)
35 mm²1.832 (33.6 mm²)1 (42.4 mm²)
50 mm²0.291/0 (53.5 mm²)1/0 (53.5 mm²)
70 mm²-1.162/0 (67.4 mm²)3/0 (85 mm²)
95 mm²-2.483/0 (85 mm²)4/0 (107 mm²)
120 mm²-3.494/0 (107 mm²)-4 (135 mm²)
A metric size does not have an AWG equivalent; these are the gauges either side. The exact gauge is the non-integer n with the same area.

How the American Wire Gauge works

The American Wire Gauge counts backwards: the bigger the number, the thinner the wire. It comes from wire drawing, where each gauge number was one more pass through a die. ASTM B258 fixes the sizes exactly. 36 AWG is 0.005 inch and 4/0 (0000) is 0.46 inch, with 39 equal ratio steps between them, so each gauge is 921/39 ≈ 1.1229 times the diameter of the next thinner one. Two handy consequences follow. Every six gauges the diameter halves, and every three gauges the area, and so the resistance, roughly doubles. 12 AWG is 2.053 mm across and 3.309 mm²; 18 AWG, six gauges thinner, is 1.024 mm.

Resistance. Resistance per length is resistivity divided by area. For annealed copper at 20 °C the international standard (IEC 60028) is 1/58 Ω·mm²/m, or 0.017241; the NIST copper wire tables express the same figure as 10.371 Ω per circular mil-foot. Hard-drawn aluminium, the grade used in conductors, is 0.028264 Ω·mm²/m, about 64% worse. 12 AWG copper measures 5.211 Ω/km, or 1.588 Ω per 1,000 ft. Resistance rises about 0.39% per °C for copper (0.40% for aluminium), so a cable at 70 °C has about a fifth more than the table shows.

Metric sizes. Most of the world sizes conductors by cross-section in mm² (IEC 60228: 1.5, 2.5, 4, 6, 10 mm² and so on). They do not line up with gauges. 2.5 mm² sits between 14 AWG (2.081 mm²) and 13 AWG (2.624 mm²); the second mode of the calculator finds the nearest gauge by area and the smallest gauge that is at least as large, which is the safe direction when substituting one for the other.

Size is not ampacity. This page gives the physical size and resistance of a gauge. How much current it may carry is a different question, answered by your electrical code’s ampacity tables, and depends on insulation temperature rating, installation method, ambient temperature and how many cables are bundled together. The same 12 AWG wire can be rated very differently in a wall, in free air or in a bundle of twenty. To size a cable for a load current and an allowed voltage drop, and to check it against the ampacity from your table, use the wire size calculator; for the voltage and power in a resistance, the Ohm’s law calculator.

Advertisement

Frequently asked questions

What is the diameter of 12 gauge wire?

2.053 mm (0.0808 in) for a solid conductor, with an area of 3.309 mm². Stranded 12 AWG has about the same copper area and is slightly larger overall.

What AWG is 2.5 mm²?

None exactly. It lies between 14 AWG (2.081 mm²) and 13 AWG (2.624 mm²). 13 AWG is the nearest and the smallest gauge at least as large; 12 AWG (3.309 mm²) is the nearest commonly stocked size above it.

How do I convert AWG to mm²?

Work out the diameter, d = 0.127 mm × 92^((36 − n)/39), then the area, π d² ÷ 4. For 1/0 to 4/0 use n = 0, −1, −2 and −3.

What is the resistance of 12 AWG copper wire?

About 5.211 Ω/km (1.588 Ω per 1,000 ft) at 20 °C. Remember the current flows out and back, so a 10 m run of two-core cable has 20 m of conductor in the loop.

Does this tell me how many amps a wire can carry?

No. Ampacity depends on the insulation, the installation method, the ambient temperature and grouping, and is set by your electrical code’s tables. Use the wire size calculator linked on this page to check a load against the ampacity from your table.

Related calculators

References

  1. ASTM B258-02. Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors. ASTM International.
  2. IEC 60028. International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C). International Electrotechnical Commission.
  3. IEC 60889. Hard-drawn aluminium wire for overhead line conductors (resistivity 0.028264 Ω·mm²/m at 20 °C).
  4. National Bureau of Standards. Handbook 100: Copper Wire Tables, 1966 (10.371 Ω·cmil/ft at 20 °C).
  5. IEC 60228:2004. Conductors of insulated cables (the metric cross-section series).