Power Factor and PF Correction Capacitor Calculator
Power Factor and PF Correction Capacitor Calculator
Your present power factor from kW and kVA — or from kW, volts and amps — then the kVAR and the microfarads of capacitance that lift it to the target, for a single-phase load or a star or delta bank at 50 or 60 Hz.
Power factor and correction
a 10 kW three-phase load drawing 12.5 kVA at 415 V, 50 Hz, corrected to 0.95 with a delta bank
Power factor and the correction capacitor
- P, S
- real power (kW) and apparent power (kVA)
- φ₁, φ₂
- phase angle before and after correction: φ = arccos(PF)
- Qc
- reactive power the capacitors must supply, in kVAR
- V
- voltage across one capacitor: VLL in delta, VLL/√3 in star
Worked example
a 10 kW three-phase load drawing 12.5 kVA at 415 V, 50 Hz, corrected to 0.95 with a delta bank
PF now = 10 ÷ 12.5 = 0.800; φ₁ = 36.9°, Q₁ = √(12.5² − 10²) = 7.50 kVAR
tan φ₁ = 0.7500, tan φ₂ = 0.3287 at PF 0.95
Qc = 10 × (0.7500 − 0.3287) = 4.21 kVAR
Delta bank: C = 4.21 kVAR ÷ (3 × 2π × 50 × 415²) = 25.96 µF per capacitor, three of them, each carrying 3.38 A
Line current falls from 17.39 A to 14.64 A, a 15.8% saving; a star bank would need 77.87 µF per capacitor instead
kVAR needed per kW of load (multiply by your kW)
| Power factor now | To 0.90 | To 0.95 | To 0.98 | To 1.00 |
|---|---|---|---|---|
| 0.60 | 0.849 | 1.005 | 1.130 | 1.333 |
| 0.65 | 0.685 | 0.840 | 0.966 | 1.169 |
| 0.70 | 0.536 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.398 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.266 | 0.421 | 0.547 | 0.750 |
| 0.85 | 0.135 | 0.291 | 0.417 | 0.620 |
| 0.90 | 0.000 | 0.156 | 0.281 | 0.484 |
What power factor is, and how a capacitor fixes it
An induction motor, a transformer and a fluorescent ballast all need a magnetising current that flows out of the supply for a quarter of each cycle and back into it for the next quarter. It does no work, but it is real current: it heats the cable, it loads the transformer and the generator, and it drags the voltage down at the end of a long run. The power factor is the fraction of the current that is actually doing something — kW ÷ kVA.
The example. A 10 kW load drawing 12.5 kVA has a power factor of 0.80 and 7.5 kVAR of reactive power. To reach 0.95 it needs 4.21 kVAR of capacitors: at 415 V, 50 Hz in delta that is 26.0 µF in each of three capacitors, or 77.9 µF each in star. The line current falls from 17.4 A to 14.6 A — 16% less current for exactly the same work — and the cable, the breaker and the transformer all get that margin back.
Why capacitors. A capacitor’s current leads the voltage by 90°, a motor’s magnetising current lags it by 90°, so putting the two side by side lets the reactive current circulate locally between them instead of travelling back to the substation. Nothing about the motor changes: it still needs its magnetising current, and the kW on the meter is the same. What changes is the current in everything upstream of the capacitor.
Where to be careful. Do not over-correct: a fixed bank sized for full load will push the power factor leading when the motor idles, which raises the voltage and can be worse than the problem. Use stepped, automatically switched banks on a varying load, and never connect a capacitor directly across a motor that is fed through a variable-speed drive. Capacitors must be discharged before handling — they hold a lethal charge after the supply is off, which is why IEC 60831-1 requires every capacitor unit to carry a discharge device (clause 22) — and they need their own protection, rated for the high inrush current at switch-on. Where the load is electronic (rectifiers, LED drivers, computer supplies) the poor power factor is caused by harmonics, not by phase shift; capacitors can resonate with the supply inductance and make things worse, and the answer is a detuned filter chosen by a specialist.
For the kVA and kW behind the ratio, see the kVA to kW calculator; for the three-phase relationships, the three-phase power calculator; for the current a corrected load draws, the watts to amps calculator.
Frequently asked questions
How do I calculate the kVAR needed to correct power factor?
Qc = kW × (tan φ₁ − tan φ₂), where φ₁ = arccos(present PF) and φ₂ = arccos(target PF). For 10 kW from 0.8 to 0.95 that is 4.21 kVAR.
What size capacitor in microfarads do I need?
C = Qc ÷ (ω V²) with Q in VAR, ω = 2πf and V the voltage across the capacitor. For a delta bank each capacitor sees the line voltage, so it needs a third of the capacitance of a star bank — but a higher voltage rating. The example above works out at 25.96 µF per capacitor in delta.
Should the bank be star or delta?
Low-voltage banks are usually delta: a third of the capacitance for the same kVAR, and no dependence on a neutral. Star banks appear at higher voltages, where the lower voltage per capacitor matters more than the extra capacitance.
Will power factor correction reduce my bill?
On a domestic kWh tariff, no — the meter counts real power. On commercial and industrial tariffs with a kVA demand charge or a power-factor penalty, yes, and often quickly. It always reduces current, so it frees up cable, breaker and transformer capacity.
Does a capacitor help with LED or computer loads?
Usually not. Their poor power factor comes from a distorted current waveform, not a phase shift, and a capacitor cannot correct distortion; it can even resonate with the supply and amplify harmonics. Those loads need active power-factor correction inside the equipment, or a detuned filter.
Related calculators
References
- ABB, Technical Application Papers No. 8: Power factor correction and harmonic filtering in electrical plants (1SDC007107G0202): Qc = P (tan φ₁ − tan φ₂), and CY = 3 × CΔ for a three-phase bank.
- Hughes E, Hiley J, Brown K, Smith I M. Electrical and Electronic Technology, 12th ed. Pearson 2016: three-phase star and delta relationships, the power triangle and power-factor improvement.
- IEC 60364-4-43:2008, Low-voltage electrical installations — Protection against overcurrent, clause 433.1: IB ≤ In ≤ IZ and I2 ≤ 1.45 × IZ.
- IEC 60831-1, Shunt power capacitors of the self-healing type for a.c. systems having a rated voltage up to and including 1 000 V — Part 1: General, clause 22 (discharge device).
