Voltage Drop Calculator
Voltage Drop Calculator
The voltage a cable loses at your load current — in volts and as a percentage — with the voltage left at the load and the power wasted as heat, for mm² or AWG, copper or aluminium, DC, single-phase or three-phase.
Voltage drop in a cable
2.5 mm² copper, 25 m one way, 16 A single-phase at 230 V, conductor at 70 °C
Voltage drop in a cable
- L
- one-way length in metres — the formula counts the return conductor
- A
- conductor cross-section in mm² (or the AWG equivalent)
- ρ₂₀, α
- copper 0.017241 Ω·mm²/m and 0.00393 /°C; aluminium 0.028264 and 0.00403
- Ploss
- I²R in every conductor: 2 I²R, or 3 I²R three-phase
Worked example
2.5 mm² copper, 25 m one way, 16 A single-phase at 230 V, conductor at 70 °C
ρ at 70 °C = 0.017241 × (1 + 0.00393 × 50) = 0.020629 Ω·mm²/m
R of one conductor = 0.020629 × 25 ÷ 2.5 = 206.3 mΩ
ΔV = 2 × 16 × 0.2063 = 6.60 V = 2.87% of 230 V
The load sees 223.4 V, and 105.6 W is lost as heat in the cable
This cable reaches 3% at 16.7 A and 5% at 27.9 A; the wire size calculator picks 2.5 mm² for exactly this circuit
The same circuit, other choices
| Change | Drop | Voltage at the load |
|---|---|---|
| As entered: 2.5 mm² copper at 70 °C | 2.87% (6.60 V) | 223.4 V |
| Same cable cold (20 °C) | 2.40% (5.52 V) | 224.5 V |
| Aluminium instead of copper | 4.72% (10.87 V) | 219.1 V |
| 4 mm² copper at 70 °C | 1.79% (4.13 V) | 225.9 V |
| Twice the length (50 m) | 5.74% (13.20 V) | 216.8 V |
| 12 AWG (3.309 mm²) copper at 70 °C | 2.17% (4.99 V) | 225.0 V |
How much voltage a cable loses
Every conductor has resistance, so current flowing along it drops voltage that never reaches the load. The drop is the current times the resistance of the whole loop — out along one conductor and back along the other — and the resistance of a conductor is its resistivity times its length divided by its cross-section. Warm conductors are worse than cold ones: copper’s resistance rises about 0.39% per degree, so a cable at its 70 °C working temperature has roughly 20% more resistance than the handbook’s 20 °C figure.
The example. 2.5 mm² copper, 25 m each way, 16 A at 230 V: each conductor is 206.3 mΩ, the drop is 6.60 V or 2.87%, the load sees 223.4 V, and 106 W disappears into warming the cable. That is 925 units a year if the circuit ran flat out continuously — the reason voltage drop is an energy question as well as a performance one.
Three-phase is different. In a balanced three-phase circuit the return currents in the three lines cancel, so the line-to-line drop is √3 × I × R rather than 2 × I × R. Enter the line-to-line voltage and the line current; the percentage is against the line-to-line figure.
How much is too much? IEC 60364-5-52’s informative Annex G suggests 3% for lighting and 5% for other uses from a public low-voltage network; the NEC’s informational notes suggest 3% on a branch circuit and 5% overall. Both are recommendations, not rules, and your local code, your distribution company and the equipment’s own tolerance decide. Motors are the loads that suffer most: torque falls with the square of the voltage, and a motor that starts sluggishly on a long run will run hot for the rest of its life.
Drop is not the only limit. A cable also has to carry its current without overheating — its ampacity — and that depends on insulation, installation method, grouping and ambient temperature, all from your code’s tables. This page says nothing about it. To go the other way and pick a size from an allowed drop, use the wire size calculator; for the physical size of a gauge, the AWG wire size calculator; for the protective device, the MCB size calculator.
Frequently asked questions
How do I calculate voltage drop?
Multiply the current by the resistance of the loop. For DC and single-phase: ΔV = 2 × L × I × ρ ÷ A, with L the one-way length in metres, A the area in mm² and ρ about 0.0172 Ω·mm²/m for cold copper (0.0206 at 70 °C). For balanced three-phase, replace the 2 with √3.
What is an acceptable voltage drop?
3% to a final circuit and 5% overall are the usual recommendations (IEC 60364-5-52 Annex G, NEC informational notes). They are advisory; equipment tolerances and your local code decide.
Why does aluminium drop more than copper?
Its resistivity is about 64% higher, so the same size drops about 64% more — 4.72% against 2.87% in the example. For the same drop it needs roughly 1.6 times the area.
Does voltage drop waste energy?
Yes. The power lost is I² × R in each conductor — heat in the wall, paid for on your meter. Halving the drop by doubling the area halves that loss.
Should I use the hot or the cold resistance?
The temperature the conductor actually reaches. Use 70 °C (or 90 °C for XLPE) for a circuit at full load, which is the conservative choice, and 20 °C only for lightly loaded runs.
Related calculators
References
- IEC 60364-5-52:2009, Annex G (informative) voltage-drop recommendations — 3% for lighting and 5% for other uses from a public low-voltage network — as tabulated in Schneider Electric’s Electrical Installation Guide.
- IEC 60228:2004 (conductor cross-sections), IEC 60028 (annealed copper, 0.017241 Ω·mm²/m at 20 °C, α = 0.00393 /K) and IEC 60889 (hard-drawn aluminium, 0.028264 Ω·mm²/m, α = 0.00403 /K).
- NFPA 70, National Electrical Code: 210.19(A)(1) and 210.20(A) (noncontinuous load plus 125% of the continuous load) and the informational notes to 210.19(A) and 215.2(A) (3% branch, 5% total voltage drop, advisory).
- IS 732:2019, Code of practice for electrical wiring installations (Bureau of Indian Standards).